Functions
3.3 Identification data
IM151-1 FO STANDARD interface module (6ES7151-1AB05-0AB0)
Manual, 02/2010, A5E01075965-03
31
2. The relevant index assigned to a particular section of the ID data is found in the
associated data record number (see the ID data table below.)
All data records which contain ID data have a length of 64 bytes.
The data record structure is based on the principle shown in the table below.
Table 3- 8 Basic structure of data records which contain ID data.
List of contents Length (bytes) Coding (hex)
Header information
SSL 2 F1 11
Index 2 00 0x
Length of identification data 2 00 38
Number of blocks which contain ID data. 2 00 01
Identification data
Index 2 00 0x
Identification data for the respective index (see table
below)
54
The identification data are assigned to the indices corresponding to the table below.
The data structures of data records 231 to 234 are compliant with the PROFIBUS Guideline -
Order No. 3.502, Version 1.1.1 dated March 2005.