Error and system messages
4.1 LED displays on the interface module
IM151-1 FO STANDARD interface module (6ES7151-1AB05-0AB0)
Manual, 02/2010, A5E01075965-03
35
Operating principle
The information about the cause of the problem is determined by means of the LED fault
display. After an announcement by means of a flashing signal, the respective error type and
after that the error location / error code are displayed.
The LED fault display of the configuration and parameter assignment errors
Is activated both during POWER ON and during operation.
Takes precedence over all other states that are displayed by the SF and BF LED.
Remains activated until the cause of the problem has been eliminated.
After a change in the ET 200S configuration, a POWER-OFF / POWER ON may be required
at the interface module.
Sequence Description
1 LEDs SF and BF flash 3x at 0.5 Hz Announcement of error type
2 LED BF flashes at 1 Hz Display of the error type (decimal)
3 LEDs SF and BF flash 3x at 2 Hz Announcement of the error location / error code
4 LED SF flashes at 1 Hz Display of the decade (decimal) of the error location /
error code
5 LED BF flashes at 1 Hz Display of the unit position (decimal) of the error
location / error code
6 Repetition of 1 - 5 until the cause of the problem has been eliminated.