EasyManuals Logo

Siemens SIMATIC ET 200S Installation And Operating Manual

Siemens SIMATIC ET 200S
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #135 background imageLoading...
Page #135 background image
Fail-Safe Modules
7.5 4/8 F-DI DC24V PROFIsafe Digital Electronic Module
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07
135
Technical Specifications
Input current
For "1" signal
3.7 mA, typical
Input delay * Assignable (for all inputs together)
Typically 0.5 ms (0.3 ms to 0.7 ms)
Typically 3 ms (2.6 ms to 3.4 ms)
For "0" after "1"
Typically 15 ms (13 ms to 17 ms)
Typically 0.5 ms (0.3 ms to 0.7 ms)
Typically 3 ms (2.6 ms to 3.4 ms)
bei "1" nach "0"
Typically 15 ms (13 ms to 17 ms)
Input characteristic In accordance with IEC 61131-2 Type 1
Connection of 2-wire proximity switch (BERO) Not possible
Permissible quiescent current
0.6 mA, maximum
Time, Frequency
Internal processing times See
"Response Times"
Acknowledgment time in safety mode
Short-circuit test activated
With input delay of 0.5 ms:
With input delay of 3 ms:
With input delay of 15 ms:
Min. 4 ms / max. 7 ms
Min. 4 ms / max. 12 ms
Min. 4 ms / max. 9 ms
Short-circuit test deactivated
Min. 4 ms / max. 6 ms
Minimum sensor signal duration See
"Minimum Duration of Sensor Signals to
Allow Correct Detection by the F-DI Module"
table in
"Wiring and Fitting Modules"
Protection against Overvoltage
Protection of power supply L+ from surge in
accordance with IEC 61000-4-5 with external
protection elements only
Symmetrical (L+ to M)
1 kV; 1.2/50 μs
Asymmetrical (L+ to PE, M to PE)
+2 kV; 1.2/50 μs
Protection of inputs and outputs from surge in
accordance with IEC 61000-4-5 with external
protection elements only
Symmetrical (Vs, DI to M)
+1 kV; 1.2/50 μs
Asymmetrical (Vs, DI to PE, M to PE)
+1 kV; 1.2/50 μs
*: With an input delay of 0.5 ms, shielded cables must be used for the digital inputs and the sensor
supply.
With 3 ms input delay, shielded cables must be used if there is a danger of overvoltage on the signal
lines (see section "Electromagnetic Compatibility") to prevent possible passivation of the fail-safe
digital inputs and the sensor power supply switching off. If unshielded signal lines are used, the safe
behavior of the process variables is ensured.
**: Operating below the permissible supply voltage is only permissible for the repair time. See chapter
"
Introduction (Page 61)."
***: For more information on the requirements for sensors and actuators, see "Wiring and Fitting
Modules".

Table of Contents

Other manuals for Siemens SIMATIC ET 200S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200S and is the answer not in the manual?

Siemens SIMATIC ET 200S Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200S
CategoryI/O Systems
LanguageEnglish

Related product manuals