Fail-Safe Modules
7.2 PM-E F pm DC24V PROFIsafe Power Module
ET 200S Distributed I/O System - Fail-Safe Modules
66 Installation and Operating Manual, 08/2008, A5E00103686-07
Capacitive Crosstalk of Digital Input/Output Signals
Readback errors may occur on the PM-E F pm DC24V PROFIsafe power module or on the
F-DO modules if the fail-safe digital output and fail-safe digital input signals are routed
through one cable. The module signals a short circuit in this situation.
Cause
The steep switching edge of the output driver during the sensor supply test of the 4/8 F-
DI DC24V PROFIsafe module may lead to crosstalk on other inactive output channels due to
the coupling capacitance of the wire, for example, on the PM-E F pm DC24V PROFIsafe
power module. This situation may lead to a response in the readback circuit in these
channels. The module detects a cross circuit and performs safety-related shutdown.
Remedy
Use separate cables for the F-DI modules and F-DO modules or standard DO modules
that are controlled by a PM-E F pm DC24V PROFIsafe.
Coupling relay or diodes in the outputs
Disable the sensor supply test if safety class requirements allow this.
See also
Assigning Modules of an ET 200S (Page 22)
Properties of the 4 F-DO DC24V/2A PROFIsafe digital electronic module (Page 163)

Table of Contents

Other manuals for Siemens SIMATIC ET 200S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200S and is the answer not in the manual?

Siemens SIMATIC ET 200S Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200S
CategoryI/O Systems
LanguageEnglish

Related product manuals