Using the High_Speed_Counter technology object
3.5 Configuring the High_Speed_Counter
Counting, measurement and position detection
114 Function Manual, 12/2017, A5E32009889-AG
Hysteresis (in increments)
By configuring the hysteresis (Page 62), you can define a range around the comparison
values. Within the hysteresis range, the digital outputs cannot switch again until the counter
value is outside the range.
Regardless of the hysteresis value, the hysteresis range ends at the low/high counting limits.
If you enter "0", the hysteresis is turned off. You can enter a value between 0and 255. The
default setting is "0".
Note
For High_Speed_Counter as of V3.0, the following applies:
You configure the hysteresis under "Behavior of DQ0" for both digital outputs together. The
hysteresis is also displayed under "Behavior of DQ1".
s is only available in operating mode "Use count value as reference".