Using the module
5.1 Using the technology module
Counting, measurement and position detection
180 Function Manual, 12/2017, A5E32009889-AG
5.1.2.5
Additional parameters for Compact CPU
Introduction
When using a Compact CPU, the following parameters are additionally available for the
signals of the high-speed counter.
Compatibility 1511C (high-speed counters of Compact CPU 1512C-1 PN)
Front connector assignment same as CPU 1511C
You can use this parameter to specify if the pin assignment for the front connector of the
CPU 1511C-1 PN is to be used for the high-speed counter of the CPU 1512C-1 PN:
Option
Meaning
Disabled (default) CPU 1512C-1 PN uses the pin assignment of the onboard front connector.
1512C-
1 PN supports the use of the connections of both front connectors of
the digital onboard I/Os for the high-speed counter. The assignment of
hardware inputs and outputs for the HSC channels is described in the CPU
1512C-1 PN manual.
Enabled CPU 1512C-1 PN uses the pin assignment of the front connector of the
CPU 1511C-1 PN. 1511C-1 PN supports the use of the connections of the
first front connector of the digital onboard I/Os for the high-speed counter.
The assignment of hardware inputs and outputs for the HSC channels is
described in the CPU 1511C-1 PN manual.
General
Activate this high-speed counter
You can use this parameter to specify whether the respective high speed counter is to be
used:
Option
Meaning
Disabled (default) The high-speed counter is not used. The counter uses no connections of
the onboard front connector and can not trigger interrupts. Writing to its
control interface is ignored and its feedback interface returns zero values.
Enabled The high-speed counter is used. The assignment of HSC addresses to the
connections of the onboard front connector is described in the device man-
ual of the Compact CPU.