Using the High_Speed_Counter technology object
3.6 Programming the High_Speed_Counter
Counting, measurement and position detection
128 Function Manual, 12/2017, A5E32009889-AG
3.6.6
Error codes of parameter ErrorID
Error code
(W#16#...)
Description
0000
No error
Error messages from technology module
80A1
POWER_ERROR from feedback interface: Incorrect supply voltage L+
80A2
ENC_ERROR from feedback interface: Incorrect encoder signal
80A3
LD_ERROR from feedback interface: Error when loading via control interface
Error messages of the instruction High_Speed_Counter
80B1
Invalid count direction
80B4 For operating mode "Use count value as reference", the following applies:
New low counting limit does not meet the following conditions:
Low counting limit < high counting limit
Low counting limit <= comparison value/start value
For operating mode "Use measured value as reference", the following applies:
New low counting limit does not meet the following conditions:
Low counting limit < high counting limit
Low counting limit <= start value
80B5 For operating mode "Use count value as reference", the following applies:
New high counting limit does not meet the following conditions:
Low counting limit < high counting limit
High counting limit >= comparison value/start value
For operating mode "Use measured value as reference", the following applies:
New high counting limit does not meet the following conditions:
Low counting limit < high counting limit
High counting limit >= start value
80B6 New start value does not meet the following condition:
Low counting limit <= start value <= high counting limit
80B7 New counter value does not meet the following condition:
Low counting limit <= counter value <= high counting limit
80B8 For operating mode "Use count value as reference", the following applies:
New comparison value 0 does not meet the following conditions:
Low counting limit <= comparison value 0 <= high counting limit
Comparison value 0 < comparison value 1
For operating mode "Use measured value as reference", the following applies:
New comparison value 0 does not meet the following conditions:
Comparison value 0 < comparison value 1