Using the High_Speed_Counter technology object
3.6 Programming the High_Speed_Counter
Counting, measurement and position detection
Function Manual, 12/2017, A5E32009889-AG
129
80B9 For operating mode "Use count value as reference", the following applies:
New comparison value 1 does not meet the following conditions:
• Low counting limit <= comparison value 1 <= high counting limit
• Comparison value 0 < comparison value 1
For operating mode "Use measured value as reference", the following applies:
New comparison value 1 does not meet the following conditions:
• Comparison value 0 < comparison value 1
80C0 Instruction High_Speed_Counter was called multiple times with the same instance (DB)
80C1 Communication with technology module failed (read data records): Error information of internal in-
struction RDREC saved in static tag AdditionalErrorID
80C2 Communication with technology module failed (write data records): Error information of internal in-
struction WRREC saved in static tag AdditionalErrorID
80C3
Access to input data (feedback interface) failed: Error information of internal instruction GETIO_PART
saved in static tag AdditionalErrorID
80C4 Access to output data (control interface) failed: Error information of internal instruction SETIO_PART
saved in static tag AdditionalErrorID
80C5 Reading of the current start information of the OB failed: Error information of internal instruction
RD_SINFO saved in static tag AdditionalErrorID
80C6 Failed to get I/O addresses of the technology module: Error information of internal instruction
RD_ADDR saved in static tag AdditionalErrorID
Module not inserted or no supply voltage L+