Using the High_Speed_Counter technology object
3.6 Programming the High_Speed_Counter
Counting, measurement and position detection
Function Manual, 12/2017, A5E32009889-AG
131
Tag
Data type
Default
Access
Description
ManualCtrlDQ0 BOOL FALSE Write Enable setting of digital output DQ0:
TRUE:
SetDQ0 sets DQ0
Control bit TM_CTRL_DQ0 = FALSE
FALSE:
Setting not enabled
Control bit TM_CTRL_DQ0 = TRUE
ManualCtrlDQ1 BOOL FALSE Write Enable setting of digital output DQ1:
TRUE:
SetDQ1 sets DQ1
Control bit TM_CTRL_DQ1 = FALSE
FALSE:
Setting not enabled
Control bit TM_CTRL_DQ1 = TRUE
UserStatusFlags
STRUCT
-
StatusDI0
BOOL
FALSE
Read
Current status of digital input DI0
StatusDI1
BOOL
FALSE
Read
Current status of digital input DI1
StatusDI2
BOOL
FALSE
Read
Current status of digital input DI2
StatusDQ0
BOOL
FALSE
Read
Current status of digital output DQ0
StatusDQ1
BOOL
FALSE
Read
Current status of digital output DQ1
1