The basics of counting, measurement and position detection
2.1 Overview of modules and properties
Counting, measurement and position detection
Function Manual, 12/2017, A5E32009889-AG
15
DI 32x24VDC HF,
DI 16x24VDC HF
CPU 1511C-1
PN,
CPU 1512C-1 PN
Number of additional
digital inputs per
3 2 — — 2
Number of physical
digital outputs per
2 2 — — 1
Number of logical
digital outputs per
2 2 — 1 2
Capture function
X X — — X
Synchronization
X X — — X
Frequency, velocity
and period duration
measurement
X X — — X
Support for isochro-
nous mode on
X (Page 75) X (Page 75) X (Page 80) X (Page 91) —
Support for diagnostic
interrupts for sensor
X (Page 66) X (Page 66) — — X (Page 66)
Hardware interrupt
X (Page 66) X (Page 66) — X (Page 90) X (Page 66)
Configurable filter for
count signals and
X X — X X
The number of available counters is dependent on the channel configuration. In order to use four counters, you must
choose the use of eight inputs in the channel configuration. If you choose the use of three inputs, you can use one coun-
ter. Other channel configurations do not allow any counter use.