Using the module
5.1 Using the technology module
Counting, measurement and position detection
186 Function Manual, 12/2017, A5E32009889-AG
Byte offset from
start address
8 LD_SLOT_1*
Specifies the significance of the value in Slot 1
0 0 0 1 Load count value (with incremental or pulse
encoder)
0 0 1 1 Load start value (with incremental or pulse
0 1 1 0 Load low counting limit (with incremental or
0 1 1 1 Load high counting limit (with incremental or
Invalid
9
Bit 7: Capture function enable
Bit 6: Enable downward synchronization (with incremental or pulse encoder)
Bit 5: Enable upward synchronization (with incremental or pulse encoder)
TM_CTRL_DQ1 Bit 2: enable technological function DQ1
Bit 1: Enable technological function DQ0
SW_GATE Bit 0: Software gate (with incremental or pulse encoder)
10
Bit 7: Count direction (for encoders without direction signal)
Bits 2 to 6: Reserve; bits must be set to 0
Bit 1: Reset of saved events
Bit 0: Reset of saved error states
Bits 0 to 7: Reserve; bits must be set to 0
If values are loaded simultaneously via LD_SLOT_0 and LD_SLOT_1, the first value is taken internally from Slot 0 and
then the value from Slot 1 is taken. This may lead to unexpected intermediate states.