EasyManua.ls Logo

Siemens SIMATIC IM 151/CPU - Examples of the Maximum Configuration

Siemens SIMATIC IM 151/CPU
218 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addressing
2-6
ET 200S Interface Module IM 151/CPU
A5E00058783-01
Address Areas for User Data Transfer with the DP Master
The ET 200S provides the PROFIBUS-DP with a maximum of 64 bytes of input
data and 64 bytes of output data. This data can be addressed in the intermediate
memory of the IM 151/CPU in up to 32 address areas.
An address area contains a maximum of 32 bytes. A maximum of 64 bytes is
available for input and output data.
The address areas start at 128 by default. The data is entered without a gap as of
address 128.
Table 2-2 Examples of the Maximum Configuration
Example
1
Example
2
Example
3
Example
4
Input address areas
Bytes per address area
16
4
2
32
16
4
0
0
Output address areas
Bytes per address area
16
4
2
32
16
2
32
2
Total no. of address areas
Total no. of bytes for inputs
Total no. of bytes for outputs
32
64
64
4
64
64
32
64
32
32
0
64
Data consistency
You define data consistency as byte, word, or overall consistency per address
area. Consistency can amount to up to 32 bytes/16 words per address area.
DP Diagnostic Address in
STEP 7
When the ET 200S is configured with
STEP 7
, a diagnostic address is set. The
ET 200S receives information on the status of the DP master or on a bus
interruption by means of this diagnostic address (see Section 4.5). In DP slave
operation the default diagnostic address is 1534.

Table of Contents

Related product manuals