5 Configuring Communication Connections
A-151
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07
IP Addresses for IP Multicast
Possible
Values
IP addresses from 224.0.0.0 to 239.255.255.255 can be used for IP multicast.
Since the IP addresses up to 224.0.0.255 are reserved for special purposes, we
recommend that you use IP addresses starting at 224.0.1.0 (default) for IP
multicast.
Identification of the Multicast Group
A multicast group is not identified using the entire IP address; the first
addressed byte and the most significant bit of the second address byte are
ignored. This is an important feature that allows seemingly different IP
addresses to address the same multicast group.
Example:
The following IP addresses address the same multicast group.
1000 0000
IP address Resulting multicast address
224.0.1.0
225.0.1.0
226.128.1.0
0.1.0
0.1.0
0.1.0

Table of Contents

Other manuals for Siemens SIMATIC NET S7-300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET S7-300 and is the answer not in the manual?

Siemens SIMATIC NET S7-300 Specifications

General IconGeneral
Product Type DesignationSIMATIC NET S7-300
MountingDIN rail mounting
Protection ClassIP20
CPU ModelsVarious models available (e.g., CPU 312, CPU 314)
Communication InterfacesMPI, PROFIBUS DP
Power Supply24 V DC power supply required. Different power supply modules available.
I/O ModulesDigital input modules, digital output modules, analog input modules, analog output modules
ProgrammingSTEP 7 software
Supply Voltage24V DC or 120/230V AC (depending on model)
Digital InputsAvailable via digital input modules
Digital OutputsAvailable via digital output modules
Analog InputsAvailable via analog input modules
Analog OutputsAvailable via analog output modules
Communication FunctionsMPI, PROFIBUS DP, Ethernet (depending on model)
ProtocolsMPI, PROFIBUS DP, TCP/IP (depending on model)
Operating Temperature0°C to 60°C
Storage Temperature70 °C
MemoryDepends on CPU model (e.g., 32 KB to 1.5 MB)