Requirements
The project is open in SIMATIC Manager in the component view.
Symbolic names were assigned for the inputs and outputs during configuration of the FF
devices.
Procedure
1. Select the folder <ProjectAS> > <CPU> > <S7 Program> in the tree structure.
2. Select the "Symbols" object in the list.
3. Select the menu command Edit > Open Object.
The "Symbol Editor" dialog box opens.
4. Make your changes.
Note
A maximum of 24 characters is permitted for a symbol.
Example: Symbol = "Status_Measurement"
5. After editing, select the menu command Table > Save.
4.4.5 How to configure interconnections to the FF devices
PCS 7 supports you during the configuration of FF devices by providing prepared templates
for different functions. In the CFC Editor, you will find the templates in catalog > "Libraries" >
tab, folder "PCS 7 AP Library V..."\Blocks+Templates\Templates.
You can find information about this in the context-sensitive help for the templates and in the
Process Control System PCS 7; Advanced Process Library
documentation.
Channel blocks for FF devices
Use the channel blocks of the PCS 7 Advanced Process Library (APL) to interconnect the
signals of FF devices.
One channel block should be used for each I/O address.
Block type Address range Block name Function block Block I/O
Analog Input FbAnIn FB 1813 PV
Output FbAnOu FB 1814 SP
Digital Input FbDiIn FB 1815 PV
Output FbDiOu FB 1816 SP