3. Select the "Load FF Segment" tab.
4. Make the settings in accordance with the table below:
Check box Application
Download FF Link
and FF devices only
in case of change
Exclude FF segment during
AS download
You configure no changes for
the FF segment, for example
The FF segment continues running during
loading if only changes are downloaded.
Always download FF
Link and FF devices
Complete download of an FF
segment
The FF segment is stopped when it is
downloaded completely.
Recommendation
After a complete download of an FF segment,
select the option "Download FF Link and FF
devices only in case of change".
Exclude FF Link and
FF devices from
download
FUNCTION for
COMMISSIONING ONLY
This function support you during
commissioning of other FF links on the same
PROFIBUS.
NOTICE!
Undefined states may occur in the FF segment
when you use this setting.
A STOP of the FF segment is possible.
See also
How to assign parameters of the FF devices (Page 33)
Commissioning
5.1 Compile and download
FOUNDATION Fieldbus