Diagnostics
System state, operating states and error displays after the failure of both PROFINET cables on
the backup CPU:
Redundant system → RUN-Redundant system state
Primary CPU/Backup CPU → RUN-Redundant operating state
MAINT LED → yellow light: The PROFINET ring is open. No backup AR.
NOTE
To get detailed diagnostics information, evaluate the diagnostics buffer.
Solution
Replace the defective PROFINET cables. You can find additional information on the procedure
in the section Replacing defective PROFINET cables (Page 326).
5.4.5.5 Failure of an interface module in an R1 device in a PROFINET ring
Introduction
The following redundancy scenario describes the effects of a failure of an interface module in
an R1 device in the PROFINET ring.
116
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
Application planning
5.4 Redundancy scenarios