New properties/functions
3
What's new in the System Manual S7‑1500R/H redundant system, issue 11/2022 compared to
issue 05/2021
What's
new?
What are the customer benefits? Where can I find the informa
tion?
Support
PROFINET system
redundancy R1
As of FW version V3.0, the S7-1500H redundant sys
tem supports PROFINET system redundancy R1:
ET 200SP IM 155-6 PN R1
(6ES7155-6AU00-0HM0)
ET 200SP HA IM 155-6 PN HA
(6DL1155-6AU00-0PM0)
ET 200iSP IM 152-1 PN (6ES7152-1BA00-0AB0)
R1 devices are equipped with two interface modules
compared to S2 devices. If one interface module
fails, the R1 device can still be reached by the H-CPUs
via the second interface module. Thus, R1 devices
have a higher availability than S2 devices.
As of System overview (Page 21)
section
New configuration vari
ants for S7-1500H
As of FW version V3.0, the S7-1500H redundant sys
tem supports additional configuration variants:
Configuration of PROFINET rings with R1 devices
Configuration of a line topology with S2 devices,
switched S1 devices
Configuration of a line topology with R1 devices
Configuration of a combined topology with R1
devices, S2 devices
Configuration without additional devices
This allows you to connect the S7-1500H redundant
system to almost any network topology and solve
complex automation tasks.
As of System overview (Page 21)
section
OB 70 As of FW version V3.0, OB 70 (I/O redundancy error)
is available for the diagnostics of R1 and S2 devices
in S7-1500H systems.
Section Basics of program editing
(Page 215)
Synchronization mod
ule up to 40 km
As of FW version V3.0, a new synchronization mod
ule Sync Module 1 GB FO 40km is available. The syn
chronization module enables a spatial distance of the
two H-CPUs of up to 40 km via optical fibers. This
allows you to use the S7-1500H redundant system
for long tunnel installations.
As of Connecting (Page 182) sec
tion
New con
tents
Data block functions As of FW version V3.0, the instructions for the data
block functions are supported:
CREATE_DB (create data block)
READ_DBL (Read from data block in the load
memory)
WRIT_DBL (Write to data block in load memory)
DELETE_DB (delete data block)
STEP7 online help
17
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD