6.3 Installing the standard rail adapter
Introduction
Use the standard rail adapter to mount the redundant SIMATIC S7-1500R/H-system on the
standardized 35mm rails.
You order the DIN rail adapter as separate accessories.
NOTE
Note the following reduced technical specifications regarding mechanical load when
you install the S7-1500R/H modules on the 35mm standard mounting rail using the
standardmounting rail adapter:
Vibration test acc. to IEC60068-2-6 (sinusoidal)
5Hz≤f≤8.4 Hz, constant amplitude 3.5mm
8.4Hz≤f≤150Hz, constant acceleration 1g
Duration of vibration: 10 frequency sweeps per axis in each of three perpendicular axes
Shock, tested according to IEC60068-2-27
Type of shock: Half-sine
Shock intensity: 150m/s
2
peak value, 11ms duration
Direction of shock: 3 shocks each in +/- direction, along each of the 3 perpendicular axes
Article No.
6ES7590-6AA00-0AA0
The scope of delivery consists of ten adapters, ten hexagon socket-head screws and ten
washers.