4.4.2 Integrated interfaces for communication
The table below provides an overview of CPU communication options in the S7‑1500R/H
redundant system.
Table 4-6S7-1500R/H communication options
Service available over:Communication option
PROFINET inter
face X1 (devices
IP
address)
PROFINET inter
face X2 (devices
IP
address)
1)
PROFINET inter
face X3 (devices
IP
address)
2)
System IP
address (on X1,
X2 and X3 inter
faces)
PROFINETIO --- --- ---
MRP (Media Redundancy Protocol) --- --- ---
LLDP (network topology detection) ---
PG communication for commissioning, testing
and diagnostics
---
HMI communication for operator control and
monitoring
3)
3)
3)
Open User Communication
3)
3)
3)
S7 communication as server
3)
3)
3)
S7 routing ---
IP forwarding
Time synchronization ---
1)
Not with CPU 1513R-1 PN
2)
Not with CPU 1513R-1 PN, CPU1515R-2 PN and CPU 1517H-3 PN
3)
Communication mainly over system IP address: If the communication partner uses a device IP address and the CPU with
this device IP address fails, communication between the communication partner and S7-1500R/H also fails.
Reference
For more information on communication options, please refer to the Communication
function manual.
4.4.3 HMI devices
HMI devices are used for machine-level process visualization and control. You use the same
HMI devices for the S7‑1500R/H redundant system as for the standard S7-1500 system.
Using HMI communication, one or more HMI devices exchange data with the CPUs . Examples
of HMI devices are HMI Basic/Comfort/Mobile Panel.
The connection of the HMI device to the redundant system depends on the specific
application. In STEP7, you can configure the following communication options:
The HMI device communicates with the redundant system over the system IP address.
The HMI device communicates with the R/H-CPUs (for example for diagnostics purposes)
over the device IP addresses.
68
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
System overview
4.4 Communication