Failure scenario
Primary CPU
Backup CPU
PROFINET cable (redundancy connections, PROFINET ring)
IO device ET 200MP
IO device ET 200SP
Switch → failed
IO device ET 200SP
HMI device
Figure 5-37Failure of a switch in the PROFINET ring (using S7-1500R as an example)
Sequence of events
1.
A switch (with additional line topology) fails in the PROFINET ring.
2.
The PROFINET ring is interrupted.
3.
If applicable, the redundant system selects an alternative connection to the IO devices
and over the backup CPU. This allows the redundant system to access all IO devices in
the PROFINET ring again.
4.
The failure of the switch has an impact on the process as the IO devices in the additional
line topology can no longer be accessed.
If the failed inputs and outputs have an important function in the system, their failure can
have a critical impact on the process.
127
Application planning
5.5 Failure scenarios
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD