EasyManua.ls Logo

Siemens Simatic S7-1500R - Page 286

Siemens Simatic S7-1500R
393 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Transition Description Effects
The primary CPU is in the RUN operating state. The redundant system switches
from the RUN-Solo system state to the SYNCUP system state if:
You set the backup CPU to RUN via the PG/PC, the display or the RH_CTRL
instruction (Mode 7) and the mode selector is set to RUN
or
You switch the mode selector on the backup CPU from STOP to RUN.
or
You POWER ON the backup CPU (mode selector to RUN)
and
the SYNCUP system state is not disabled by the RH_CTRL instruction.
RUN → RUN-Syncup
The primary CPU switches from the RUN operating state to the RUN-Syncup
operating state if:
You set the backup CPU to RUN via the PG/PC or the display and the mode
selector is set to RUN
or
You switch the mode selector on the backup CPU from STOP to RUN.
or
You POWER ON the backup CPU (mode selector to RUN).
Operating state
transitions
STOP → SYNCUP
The backup CPU switches from the STOP operating state to the SYNCUP operat
ing state.
See section SYNCUP sys
tem state (Page 270)
SYNCUP → RUN-Redundant, RUN-Syncup → RUN-Redundant
Transition Description Effects
System state trans
ition
SYNCUP → RUN-Redundant
The redundant system switches from SYNCUP to the RUN-Redundant system
state if SYNCUP has successfully run.
In the RUN-Redundant system state, the two CPUs execute the user program
synchronously.
Note: A temporary increase in the cycle time can occur upon a system
state transition SYNCUP → RUN-Redundant. Configure a sufficiently long
maximum cycle time for the CPUs.
RUN-Syncup → RUN-Redundant
The primary CPU switches from the RUN-Syncup operating state to the RUN-
Redundant operating state if SYNCUP has successfully run.
Operating state
transitions
SYNCUP → RUN-Redundant
The backup CPU switches from the SYNCUP operating state to the RUN-
Redundant operating state if SYNCUP has successfully run.
This system state trans
ition does not have any
effect on data.
Communication connec
tions (HMI, PG/PC) on
the backup CPU become
available.
Both CPUs process the
user program synchron
ously.
286
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
Commissioning
11.4 Operating and system states

Table of Contents

Other manuals for Siemens Simatic S7-1500R

Related product manuals