SYNCUP → RUN-Solo, RUN-Syncup → RUN
Transition Description Effects
System state trans
ition
SYNCUP → RUN-Solo
The redundant system switches from the SYNCUP system state to the RUN-Solo
system state if:
You execute POWER OFF for the backup CPU
or
The redundant system detects an error during SYNCUP that prevents
redundant operation
or
You set the backup CPU to STOP with the PG/PC, the display or the mode
selector.
This system state trans
ition does not have any
effect on data.
Primary CPU oper
ating state trans
ition
RUN-Syncup → RUN
The primary CPU switches from the RUN-Syncup operating state to the RUN
operating state and continues to execute the user program.
These operating state
transitions have no
effect on data.
SYNCUP → STOP, RUN-Syncup → STOP
Transition Description Effects
System state trans
ition
SYNCUP → STOP
The redundant system switches from the SYNCUP system state to the STOP sys
tem state if:
You set the primary CPU or both CPUs to STOP with the PG/PC, the display
or the mode selector.
SYNCUP Is aborted as a result of an error in the primary CPU or in both
CPUs.
This system state trans
ition does not have any
effect on data.
RUN-Syncup → STOP
The primary CPU switches from the RUN-Syncup operating state to the STOP
operating state if:
The primary CPU detects an error that prevents further processing
or
You set the primary CPU to STOP with the PG/PC, the display or the mode
selector
or
The redundant system processes a STOP command in the user program.
Operating state
transitions
SYNCUP → STOP
The backup CPU restarts and switches to the STOP operating state after SYN
CUP aborts if:
SYNCUP Is aborted due to an error (for causes and remedies, see section
SYNCUP system state (Page 270))
or
You set the CPU to STOP with the PG/PC, the display or the mode selector.
These operating state
transitions have no
effect on data.
288
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
Commissioning
11.4 Operating and system states