Figure 11-11Primary CPU switches to the RUN operating state
Table 11-14Response to loss of redundancy of CPU: Primary CPU switches to RUN
No. in
diagram
Primary CPU System state Backup CPU
Initial situation: The S7‑1500R/H redundant system is in the RUN-Redundant system state.
The backup CPU fails because of a hardware defect.
①
The CPU switches from RUN-Redund
ant to RUN. The CPU behaves like a
standard CPU and continues to pro
cess the user program.
RUN-Redundant → RUN-Solo Following the error, the CPU switches from
the RUN-Redundant operating state to
STOP or POWER OFF.
Error elimination procedure for redundant operation
1.
Eliminate the error.
2.
Start the backup CPU.
The backup CPU switches from the STOP operating state to the SYNCUP operating state.
Synchronization starts as detailed in the section SYNCUP system state (Page 270).
291
Commissioning
11.4 Operating and system states
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD