Climatic ambient conditions
The table below shows the permissible climatic environmental conditions for the SIMATIC
S7-1500R/H redundant system during operation.
Table 15-8Climatic ambient conditions
Ambient conditions Permissible range Comments
from 0 to 60°C
Article No. 6ES7513-1RL00-0AB0,
6ES7515-2RM00-0AB0:
Horizontal
mounting pos
ition
from -30 to 60°C
Article No. 6ES7513-1RM03-0AB0,
6ES7515-2RN03-0AB0:
from 0 to 40°C
Article No. 6ES7513-1RL00-0AB0,
6ES7515-2RM00-0AB0:
Temperature R-
CPUs
Vertical
mounting pos
ition
from -30 to 40°C
Article No. 6ES7513-1RM03-0AB0,
6ES7515-2RN03-0AB0:
from 0 to 60°CHorizontal
mounting pos
ition
from 0 to 55°C
with synchronization modules Sync
Module 1 GB FO 40km
(6ES7960-1FE00-0AA5)
1)
from 0 to 40°C
Temperature H-
CPUs
Vertical
mounting pos
ition
from 0 to 35°C
with synchronization modules Sync
Module 1 GB FO 40km
(6ES7960-1FE00-0AA5)
1)
To increase the service life of the display, the dis
play switches off when the permitted operating
temperature is exceeded.
At certain temperatures, the display switches off
and on again. You can find more information in
the technical specifications in the CPU manuals.
Temperature vari
ation
10 K/h -
Relative humidity from 10 % to 95 % Without condensation
Barometric pres
sure
From 1140 to 795hPa Corresponds to an altitude of -1000mto2000m.
Note the following section "Using the redundant
S7-1500R/H system over 2000m above sea level".
Pollutant concen
tration
ANSI/ISA-71.04 severity level G1; G2;
G3
-
1)
If you use the Sync Module 1 GB FO 40 km (6ES7960-1FE00-0AA5) synchronization modules in the H-CPUs, then restric
tions apply to the maximum ambient temperature.
Using the redundant S7-1500R/H system over 2000m above sea level
Table 15-9R/H CPUs for maximum installation altitude 5000m
CPU designation Article number Version Max. installation
altitude
CPU 1513R-1 PN 6ES7513-1RL00-0AB0
6ES7513-1RM03-0AB0
FS01 or higher 5,000m
362
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
Technical specifications
15.4 Mechanical and climatic ambient conditions

Table of Contents

Other manuals for Siemens Simatic S7-1500R

Related product manuals