5.6 Parameters for SIMODRIVE POSMO A
5-209
Siemens AG 2013 All Rights Reserved
SIMODRIVE POSMO A User Manual (POS1) – 08/2013 Edition
P0023 / 17 Jerk time constant
300W 075W
Min Standard Max Unit Data type Effective
0 0 400 ms T4 immed.
The acceleration/deceleration is changed over this time.
Note:
Input resolution = 10 ms
P0024 / 18 Override velocity
300W 075W
Min Standard Max Unit Data type Effective
0 16384 16384 % N2 immed.
Closed-loop speed control: referred to P8 (maximum speed)
Closed-loop position controlled: referred to P10 (maximum velocity)
Note:
The parameter value can be changed while traversing.
P0025 / 19 Override acceleration
300W 075W
Min Standard Max Unit Data type Effective
0 16384 16384 % N2 immed.
Closed-loop speed control: referred to P9 (acceleration time)
P25 = 50% means: Doubling of ramp up time
P25 = 10% means: Multiplication by 10 of ramp up time
Closed-loop position controlled: referred to P22 (maximum acceleration)
The following applies from SW 2.0:
The acceleration override can be changed with immediate effect in the ”Speed setpoint” oper-
ating mode.
This is also possible when the drive is moving.
P0026 / 1A Override speed, jogging
300W 075W
Min Standard Max Unit Data type Effective
0 3276 16384 % N2 immed.
Referred to P8 (maximum speed).
Is calculated in addition to P24 (override velocity).
Note:
The parameter value can be changed while traversing.
P0027 / 1B Override acceleration, jogging
300W 075W
Min Standard Max Unit Data type Effective
0 8192 16384 % N2 immed.
Refer to P9 (acceleration time).
Is calculated in addition to P25 (override acceleration).
5 Description of the Functions
02.9904.0108.06