5.2 Networking
SIMOTION C
124 Operating Instructions, 02/2012
Example
The following figure shows an example configuration of a subnet with SIMOTION C.
ᆯ
ᆯ
ᆯ
ᆱ
ᆱ
ᆱ
ᆱ
ᆯ ᆯ
ᆯ
ᆯ
ᆱ
'ULYH
6,02'5,9(
XQLYHUVDO
PD[FDEOHOHQJWKP
IURPWHUPLQDWLQJUHVLVWRUWRWHUPLQDWLQJUHVLVWRU
ᆯ7HUPLQDWLQJUHVLVWRUHQDEOHG
ᆰ'3PDVWHU
ᆱ'3VODYH
WR[352),%86'3DGGUHVVHVRIQRGHV
0D[P
1HWZRUN
1HWZRUN
6XSSO\
V\VWHP
+LJKHVW352),%86DGGUHVV 3RVVLEOH352),%86QRGHV
WR
WR
36
36
;;
56
5HSHDWHU
3*
6,027,21&
36
;
;
36 ,0
6060 60
6
03
6,027,21&
&38
(70
0%DXG

Figure 5-19 Networking example
Segment in subnet
The baud rate determines the cable length of a subnet segment (see the following table).
Table 5- 8 Permitted cable lengths of a subnet segment for specific baud rates
Baud rate Max. cable length of a segment (in m)
9.6 to 187.5 bits/s 1000
1)
500 Kbits/s 400
1.5 Mbit/s 200
3 to 12 Mbits/s 100
1)
With isolated interface