Supplementary system components
6.4 Controller Extension CX32
SIMOTION D4x5
Manual, 02/2012
99
Ambient conditions
Table 6- 22 CX32 environmental requirements
Parameter Values
Permissible ambient temperature
Storage and transport
Operation
-40° C ... +70° C
0° C to +55° C up to 2000 m above sea level
As of an altitude of 2000 m, the maximum ambient
temperature decreases by 7° C every 1000 m
Permissible relative humidity
(without condensation)
5 % ... 95 %
Installation altitude Max. 5000 m above sea level
Organic/biological influences
Storage
Transport
Operation
Class 1B1 according to EN 60 721-3-1
Class 2B1 according to EN 60 721-3-2
Class 3B1 according to EN 60 721-3-3
Pollution degree 2 according to EN 60 664-1
Degree of protection according to EN 60529
(IEC 60529)
IP20
Atmospheric pressure 700 ... 1060 hPa
Integrated drive control
Table 6- 23 Controls for integrated drives
Data SIMOTION CX32
Max. number of axes for integrated drive
control (servo/vector/
V
/
f
)
6 / 4 / 8 (alternative)
Drive control based on SINAMICS S120 CU320,
firmware version V2.x
Communication
Table 6- 24 Interface communication
Data SIMOTION CX32
DRIVE-CLiQ interfaces 4

Table of Contents