Supplementary system components
6.3 TB30 terminal board
SIMOTION D4x5
84 Manual, 02/2012
6.3.3.4 Digital inputs/outputs
Table 6- 5 Terminal block X481
Terminal Designation
1)
Technical specifications
1 DI 0
2 DI 1
3 DI 2
4 DI 3
Voltage: -3 V to 30 V
Typical current consumption: 10 mA at 24 VDC
Ground reference: X424 (G terminal)
Input delay:
L ⇒ H: approx. 20 μs
H ⇒ L: approx. 100 µs
Level (including ripple):
High signal level: 15 V to 30 V
Low signal level: -3 V to 5 V
5 DO 0
6 DO 1
7 DO 2
8 DO 3
Voltage: 24 VDC
Max. load current per output: 500 mA
Ground reference: X424 (M terminal)
Continuous short-circuit-proof
output delay:
L ⇒ H: Typically 150 μs at 0.5 A ohmic load (500 μs max.)
H ⇒ L: Typically 50 μs at 0.5 A ohmic load
Switching frequency:
With resistive load: max. 100 Hz
With inductive load: max. 0.5 Hz
With lamp load: max. 10 Hz
Maximum lamp load: 5 W
1) DI: digital input, DO: Digital output