09.02  Start-Up 
Siemens AG    6SE7087-6AK85-1AA0 
4-31 
Rectifier/Regenerating Unit    Operating Instructions 
4.3.5 Analog output 
1 analog output, which can be parameterized,
 at the control terminal strip (board CUR, -X102 / Section 3.3) 
to output actual values and other internal rectifier/regenerating unit quantities. 
  Analog output:  - Voltage range: ± 10V  
    - Resolution: 39mV (8 bits + sign) 
  - Accuracy: ± 5% 
    - Smoothing: 20ms 
    - Output current: max. ± 5mA 
    - Short-circuit proof and non-floating 
 
Connecting-up:
 
  Refer to "Control terminal strip", Section 3.3 
 
Parameterization:
 
  Also observe "Function diagram, analog output CUR", Section 4.4! 
 
♦  Enter the parameter number (0 to 999) whose value is to output, in P655 "CUR-AA actual values". 
 
♦  Set the analog output gain factor in P656 "CUR-AA gain". 
  (setting range: -320.00V to +320.00V  /  pre-setting: +10.00V ⇔ gain of 1) 
 
♦  Set the offset in P657 "CUR-AA offset". 
  (setting range: -100.00V to +100.00V  /  pre-setting: +0.00V ⇔ no offset) 
 
The following is obtained for the calculation from the "Function diagram, analog output CUR": 
 
]
[]
[] []
VinOffsetVinainG
%100
%nivalue Parameter
Uoff +
⎟
⎟
⎠
⎞
⎜
⎜
⎝
⎛
×=
 
 
Pre-assignment (gain of 1 and no offset):  100% = 10V 
 
The parameter value in [%] for the appropriate parameter number can be taken from the parameter list,  
Chapter 5!  
 