Start-Up  09.02 
4-10  Siemens AG    6SE7087-6AK85-1AA0 
  Rectifier/Regenerating Unit    Operating Instructions 
4.2.5  Simple application examples for connecting process data with connection assignment 
Connecting-up: Refer to Section 3.3 "Control terminal strip" 
 
Factory setting: 
Switch-on/off via the PMU, messages and actual values via the terminal strip. 
Terminal strip only operational if binary input 5 (BE5) is energized (high signal level corresponds to "reserve"). 
 
 
 
CUR PMU
P554.1 = 1010
ON/OFF1
Floating contact
Fault
ON/OFF1
OFF2 (pulse inhibit)
Acknowledge
Basic
/reserve 
(activates above commands)
Actual Ud value
P603.1 = 1002 
P554.2 = 1001
P555.2 = 1002
P565.2 = 1003
P590    = 1005
P655.1 = 37
-X104/19  BA2
-X104/20  BA2
-X101/6    P24
-X101/9    BE1
-X101/10  BE2
-X101/11  BE3
-X101/12  BE4
-X101/13  BE5
-X102/15  AAM
-X102/14  AA
 
 
Manual/automatic operation: 
Automatic operation (BE5 high signal level):  Command input from the automation unit via serial interface 
(SST1), the monitoring of external faults via a terminal strip also 
possible. 
Manual operation (BE5 low signal level):  Command input via the terminal strip. 
 
 
 
CUR                    SST1
P554.2 = 2001
P565.2 = 2001
SST
ON/OFF1
Acknowledge
Actual Ud value
Floating contact
Operation
ON/OFF1
Acknowledge
Fault external 1
Basic
/reserve
Automation unit
P602.1 = 1002
P554.1 = 1001
P565.1 = 1003
P575.1 = 1004
 P575.2 = 1004  (always activ)
P590    = 1005
P655 = 37
-X104/19  BA2
-X104/20  BA2
-X101/6    P24
-X101/9    BE1
-X101/10  BE2
-X101/11  BE3
-X101/12  BE4
-X101/13  BE5
-X102/15  AAM
-X102/14  AA
 
 