09.02 Fault and Alarm Messages
Siemens AG 6SE7087-6AK85-1AA0
7-3
Rectifier/Regenerating Unit Operating Instructions
Fault
No.
Fault description
Fault
value
Meaning Possible causes
Countermeasures
F022 I
2
t Overload
I
2
t monitor of the power section has
responded
The monitor responds when 100 % of the
calculated I
2
t value of the power section is
reached.
- - - Drive operated too long under
overload conditions
- Check to see whether the rated
current of the R/G unit is
adequate for the specific
application
- See also P785
F023 LT-Temp.
Temperature of the power section too high
A check is made to see whether the heat
sink temperature measured using
thermistor(s) is > 95 °C (or 123,9°C)
1
Heat sink temperature > 95 °C
or with water-cooled units:
heat sink temperature > 123,9 °C
- Heat sink (air inlets and outlets)
contaminated
- Heat sink temperature sensor not
connected to X31, X32 on A1681
and/or A1682 module (“slave
unit”)
- Fan has no voltage
- Fan faulted
- Fan running in the wrong
direction
- Fan fuse (F3, F4) defective
NOTE:
- Measure inlet air ambient
temperature. If ϑ > 40 ºC, note
reduction curves. See Section
14.1.
With water-cooled units:
- Water inlet temperature too high,
cooling circuit interrupted or
cooling water pump faulty
Temperature of the power section too low 2
Heat sink temperature -45 °C
- Heat sink temperature sensor not
connected to X30 module on
A1681 and/or A1682
F029 Measure Flt
Fault in line voltage measurement
An offset > 5% has been detected when
attempting to compensate for the offset of
the line voltage measurement
1
2
3
4
Channel V-U faulted
(regenerative feedback
direction)
Channel V-W faulted
(regenerative feedback
direction)
Channel W-U faulted
(regenerative feedback
direction)
Channel W-U faulted
(infeed direction)
- Fault in the voltage path on the
power interface module (A1681
and/or A1682 and/or A1685) or
on the electronic module (CUR)
F030 DC Bus Short
DC link short-circuit
The monitor responds if the following
conditions obtain for longer than 0.5 sec:
- The current limit of the
rectifier/regenerating unit is reached
(this condition does not apply during
circuit identification or during DC link
forming)
- The rectifier or regenerative current is
greater than 10% of the rated DC
current (P075)
- The DC link voltage is less than 5% of
1.35*P071
- - - Short-circuit in the DC link
F031 Fuse Blown
Fuse blown in a thyristor branch of the
rectifier/regenerating unit or of a parallel
power section.
- - - Thyristor branch fuse faulted
F032 Phase Sequ.?
Wrong phase sequence
A check is make to see whether the phase
sequence of the rectifier bridge is the
same as that of the regenerative bridge.
- - - Phase sequence of the rectifier
bridge different from that of the
regenerative bridge
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simovert 6SE70 Series and is the answer not in the manual?

Siemens Simovert 6SE70 Series Specifications

General IconGeneral
BrandSiemens
ModelSimovert 6SE70 Series
CategoryDC Drives
LanguageEnglish

Related product manuals