Fault and Alarm Messages 09.02
7-6 Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
Fault
No.
Fault description
Fault
value
Meaning Possible causes
Countermeasures
F066 SST2 Telegr.
Peer-to-peer telegram to SST1 failed
Following receipt of a valid telegram, no
further telegrams were received for longer
than the time set with parameter
P687.i003
- - - Cable break
F070 SCB Initial
SCB initialization error
An error has occurred when initializing the
SCB.
1
2
5
6
10
SCB not plugged in or SCB module
code wrong
SCB not compatible
Wrong initialization data
Timeout when initializing
Error in the configuration channel
- Plug in the SCB
- Check the SCB and/or replace it
- Correct the initialization data
F072 SCB Heartb.
SCB heartbeat
SCB no longer processes the heartbeat
counter.
- - - Replace the SCB
- Check the connection between
the module rack and the option
module
F073 Sl1 AnaIn1
Current at analog input 1, slave 1, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 1) -X428:4, 5
F074 Sl1 AnaIn2
Current at analog input 2, slave 1, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 2) -X428:7, 8
F075 Sl1 AnaIn3
Current at analog input 3, slave 1, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 3) -X428:10, 11
F076 Sl2 AnaIn1
Current at analog input 1, slave 2, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 3) -X428:4, 5
F077 Sl2 AnaIn2
Current at analog input 2, slave 2, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 3) -X428:7, 8
F078 Sl2 AnaIn3
Current at analog input 3, slave 2, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 3) -X428:10, 11
F079 SCB Telegr.
SCB telegram failure
Following a correctly received telegram,
no further telegram has been received
within the time set with parameter
P687.i002.
- - - Check connection to the SCB
F080 TB/CB Init.
An error has occurred when initializing the
module at the DPR interface.
1
2
5
6
7
TB/CB not plugged in
TB/CB not compatible
Error in initializing data
Timeout when initializing
TB/TC module code wrong
- Contact problem in connection
between module rack and TB
and/or CB
- Slot does not agree with
assignment (P090, P091)
- Wrong module code r723
- Wrong module compatibility r724
F081 TB/CB Heartb
TB/CB heartbeat error
TB or CB has stopped processing the
heartbeat counter.
- - - Contact problem in connection
between module rack and TB
and/or CB
- Hardware fault (replace TB and/or
CB)
AoteWell Automation Sales Team
Buy Siemens PLC HMI Drives at AoteWell.com