Fault and Alarm Messages 09.02
7-6 Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
Fault
No.
Fault description
Fault
value
Meaning Possible causes
Countermeasures
F066 SST2 Telegr.
Peer-to-peer telegram to SST1 failed
Following receipt of a valid telegram, no
further telegrams were received for longer
than the time set with parameter
P687.i003
- - - Cable break
F070 SCB Initial
SCB initialization error
An error has occurred when initializing the
SCB.
1
2
5
6
10
SCB not plugged in or SCB module
code wrong
SCB not compatible
Wrong initialization data
Timeout when initializing
Error in the configuration channel
- Plug in the SCB
- Check the SCB and/or replace it
- Correct the initialization data
F072 SCB Heartb.
SCB heartbeat
SCB no longer processes the heartbeat
counter.
- - - Replace the SCB
- Check the connection between
the module rack and the option
module
F073 Sl1 AnaIn1
Current at analog input 1, slave 1, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 1) -X428:4, 5
F074 Sl1 AnaIn2
Current at analog input 2, slave 1, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 2) -X428:7, 8
F075 Sl1 AnaIn3
Current at analog input 3, slave 1, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 3) -X428:10, 11
F076 Sl2 AnaIn1
Current at analog input 1, slave 2, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 3) -X428:4, 5
F077 Sl2 AnaIn2
Current at analog input 2, slave 2, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 3) -X428:7, 8
F078 Sl2 AnaIn3
Current at analog input 3, slave 2, under 4
mA
- - - Check the connection between
the signal source and the SCI1-
module (slave 3) -X428:10, 11
F079 SCB Telegr.
SCB telegram failure
Following a correctly received telegram,
no further telegram has been received
within the time set with parameter
P687.i002.
- - - Check connection to the SCB
F080 TB/CB Init.
An error has occurred when initializing the
module at the DPR interface.
1
2
5
6
7
TB/CB not plugged in
TB/CB not compatible
Error in initializing data
Timeout when initializing
TB/TC module code wrong
- Contact problem in connection
between module rack and TB
and/or CB
- Slot does not agree with
assignment (P090, P091)
- Wrong module code r723
- Wrong module compatibility r724
F081 TB/CB Heartb
TB/CB heartbeat error
TB or CB has stopped processing the
heartbeat counter.
- - - Contact problem in connection
between module rack and TB
and/or CB
- Hardware fault (replace TB and/or
CB)
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simovert 6SE70 Series and is the answer not in the manual?

Siemens Simovert 6SE70 Series Specifications

General IconGeneral
BrandSiemens
ModelSimovert 6SE70 Series
CategoryDC Drives
LanguageEnglish

Related product manuals