EasyManuals Logo

Siemens Simovert 6SE70 Series User Manual

Siemens Simovert 6SE70 Series
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #264 background imageLoading...
Page #264 background image
Technical Data 09.02
14-4 Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
R/R unit 6SE70..-.....-1AA0 38-2EH85 41-0EH85 41-3EK85 41-8EK85
Rated voltage, rated frequency, rated current
Rated voltage
Rectifier connection
Regenerative connection
DC link voltage
V
3AC 380V –15% to 480V +10%
using an (auto) transformer
1.2 times the voltage of the rectifier connection
DC 510V –15% to 650V +10%
Rated frequency f
n
Input
Output
Hz
46 to 64 (automatic frequency matching)
DC
Rated current
(rms value)
With autotransformer
Regenerating, line
side
Regenerating, unit
side
Rectifier operation
Without autotransformer
Regenerating, unit
side
Rectifier operation
A
784
654
710
654
710
980
817
888
817
888
1276
1064
1156
1064
1156
1702
1481
1542
1481
1542
Load class I to EN 60146-1-1 of the DC link current (average value)
in rectifier operation; currents reduced to 92% in regenerative operation
Rated current
(average)
DC link connection
Rectifier operation
A 821 1023 1333 1780
Load class II to EN 60146-1-1 of the DC link current (average value)
in rectifier operation; currents reduced to 92% in regenerative operation
Rated current A 747 931 1213 1620
Base load duration s 240
Excess current A 1121 1396 1820 2430
Excess current duration s 60
Losses, cooling
Power dissipation
Maximum
kW 3.29 3.70 4.84 6.24
Cooling air requirement m
3
/s 0.55 0.55 1.0 1.0
Sound pressure level, dimensions, weight
Sound pressure level 50 Hz
60 Hz
dB(A) 80
83
80
83
82
82
82
82
Size
Width
Height
Depth
mm
mm
mm
H
508
1400
551
H
508
1400
551
K
800
1725
550
K
800
1725
550
Weight app. kg 175 175 450 470
Parallel units (-1AD0) of size K for connecting in parallel have the same technical data as the corresponding
"basic units" (-1AA0). Please note the unit correspondence and notes of Section 3.7!
The permissible output current in parallel mode is reduced (due to current division between the power sections)
by 10 % as compared to the sum of the rated currents of the separate power sections.
https://www.aotewell.com
AoteWell Automation Sales Team
Sales@aotewell.com
AoteWell LTD
Buy Siemens PLC HMI Drives at AoteWell.com
https://www.aotewell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simovert 6SE70 Series and is the answer not in the manual?

Siemens Simovert 6SE70 Series Specifications

General IconGeneral
BrandSiemens
ModelSimovert 6SE70 Series
CategoryDC Drives
LanguageEnglish

Related product manuals