Installation
3.2 System Installation
Distributed converter for SIMOGEAR geared motors
Getting Started, 04/2018, FW V4.7 SP10, A5E36100338B AG
43
16.
Final connection and adjustments
1.
Connect the temperature sensor connector into the
connector at the top edge of the CPI.
2.
Connect the small communications connector into the
connector at the top of the CPI.
3.
Connect the large communications connector into the
connector on the top of the Control Module.
4.
Connect the CPI ribbon cable to the connector on the top of
the Control Module.
5.
Configure the DIP switches to the requirements of the
application (see Step 17 below).
Note:
The PROFIBUS/PROFINET communications cable is not pre
-
fitted to the Control Module, it is part of the accessories su
p-
plied in the product packaging.
17.
PROFIBUS / USS address and basic commissioning DIP-
switches
There are three sets of DIP
-switches that allow the user to
configure the network device address and perform a basic
commissioning of the system.
Quick Commissioning with DIP switches (Page 75)
18.
PROFIBUS / USS network termination switch
When using the PROFIBUS or USS communications prot
o-
cols, the last converter on the network must have the network
termination switch in the
ON position.
19.
Fit memory card into the Power Module
To allow parameter settings to be stor
ed or copied to the con-
verter, the memory card must be fitted into the memory card
reader.