Control optimization required
In some cases, the self optimization result is not satisfactory, or self optimization is not possible
as the motor cannot freely rotate.
W
Initially, the speed actual value follows the speed setpoint with
some delay, and then overshoots the speed setpoint.
W
First, the actual speed value increases faster than the speed
setpoint. Before the setpoint reaches its 󹪝nal value, it passes the
actual value. Finally, the actual value approaches the setpoint
without any signi󹪝cant overshoot.
In the two cases describe above, we recommend that you manually optimize the speed
control.
Optimizing the speed controller
Requirements
Torque precontrol is active: p1496 = 100%.
The load moment of inertia is constant and independent of the speed.
The converter requires 10%… 50% of the rated torque to accelerate.
When necessary, adapt the ramp-up and ramp-down times of the ramp-function generator
(p1120and p1121).
Procedure
1. Switch on the motor.
2. Enter a speed setpoint of approximately 40%of the rated speed.
3. Wait until the actual speed has stabilized.
4. Increase the setpoint up to a maximum of 60% of the rated speed.
5. Monitor the associated characteristic of the setpoint and actual speed.
6. Optimize the controller by adapting the ratio of the moments of inertia of the load and motor
(p0342):
W
Initially, the speed actual value follows the speed setpoint with
some delay, and then overshoots the speed setpoint.
Increase p0342
W
Initially, the speed actual value increases faster than the speed
setpoint. The setpoint passes the actual value before reaching its
󹪝nal value. Finally, the actual value approaches the setpoint with‐
out any overshoot.
Reduce p0342
Advanced commissioning
8.20Motor control
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 313

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals