Suppressing the automatic restart only functions for the setting p1210=6, 16 or 26.
Note
Motor starts in spite of an OFF command via the 󹪝eldbus
The converter responds with a fault if 󹪝eldbus communication is interrupted. For one of the
settings p1210 = 6, 16 or 26, the converter automatically acknowledges the fault and the motor
restarts, even if the higher-level control attempts to send an OFF command to the converter.
In order to prevent the motor automatically starting when the 󹪝eldbus communication fails,
you must enter the fault number of the communication error in parameter p1206.
Parameter
Number Name Factory setting
p1206 Automatic restart faults not active 0
p1210 Automatic restart mode 0
p1211 Automatic restart, start attempts 3
p1212 Automatic restart, wait time start attempts 1s
p1213[0] Automatic restart monitoring time
for restart
60s
p1213[1] Reset automatic restart monitoring time for
startup counter
0s
8.30 Kinetic bu󹪜ering (Vdc min control)
Overview
Kinetic bu󹪜ering increases the drive availability. The kinetic bu󹪜ering utilizes the kinetic
energy of the load to bu󹪜er line dips and failures. During a line dip, the converter keeps the
motor in the switched-on state for as long as possible. One second is a typical maximum
bu󹪜er time.
Requirement
The following requirements must be ful󹪝lled to practically use the "kinetic bu󹪜ering" function:
The driven machine has a su󹪟ciently high inertia.
The application allows a motor to be braked when the line supply fails.
Advanced commissioning
8.30Kinetic bu󹪜ering (Vdc min control)
SINAMICS G120C Converters
350 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals