Function description
When the line supply dips or is interrupted, the DC-link voltage in the converter decreases. The
kinetic bu󹪜ering (V
DC min
control) intervenes at an adjustable threshold. The V
DC min
control forces
the load to go into slightly regenerative operation. As a consequence, the converter covers its
power loss and the losses in the motor with the kinetic energy of the load. The load speed
decreases, but the DC-link voltage remains constant during the kinetic bu󹪜ering. After the line
supply returns, the converter immediately resumes normal operation.
'&OLQNYROWDJH
0RWRULQJ
*HQHUDWLQJ
2SHUDWLRQ
6SHHG
9
'&PLQ
FRQWUROOHULV
DFWLYH
3RZHUIDLOXUH
U
S
W
W
W
W
Figure8-74 Principle mode of operation of kinetic bu󹪜ering
Parameter
Parameter Description Factory setting
r0056[0…15] CO/BO: Status word, closed-loop control -
p0210 Device supply voltage 400V
p1240[D] Vdc controller con󹪝guration (vector control) 1
p1245[D] Vdc_min controller switch-in level (kinetic bu󹪜ering) 73%…76%
r1246 Vdc_min controller switch-in level (kinetic bu󹪜ering) - V
p1247[D] Vdc_min controller dynamic factor (kinetic bu󹪜ering) 300%
p1255[D] Vdc_min controller, time threshold 0s
p1257[D] Vdc_min controller, speed threshold 50rpm
Advanced commissioning
8.30Kinetic bu󹪜ering (Vdc min control)
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 351

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating