5. Repeat steps 2 and 3 as often as required until the converter outputs fault F01018.
6. Now set p0971=1.
7. Switch o󹪜 the converter power supply.
8. Wait until all LEDs on the converter are dark. Then switch on the converter power supply
again.
The converter now powers up with the factory settings.
9. Recommission the converter.
You have restored the converter factory settings.
The motor cannot be switched-on
If the motor cannot be switched-on, then check the following:
Is a fault present?
If there is, then remove the fault cause and acknowledge the fault.
Has the converter been completely commissioned p0010 = 0?
If not, the converter is e.g. still in a commissioning state.
Is the converter reporting the "ready to start" status (r0052.0 = 1)?
Is the converter missing some enable signals (r0046)?
How does the converter receive its setpoint and commands?
Digital inputs, analog inputs or 󹪝eldbus?
Corrective maintenance
10.7If the converter no longer responds
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 419

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals