Routing cables outside the control cabinet
Maintain a minimum clearance of 25 cm between cables with a high level of interference and
cables with a low level of interference.
Use shielded cables for the following connections:
Converter motor cable
Cable between the converter and braking resistor
Signal and data cables
Connect the motor cable shield to the motor enclosure using a PG gland that establishes a
good electrical connection.
Requirements relating to shielded cables
Use cables with 󹪝nely-stranded, braided shields.
Connect the shield to at least one end of the cable.
Figure4-5 Examples for EMC-compliant shield support
Attach the shield to the shield support directly after the cable enters the cabinet.
Do not interrupt the shield.
Only use metallic or metallized plug connectors for shielded data cables.
Installing
4.2EMC-compliant setup of the machine or plant
SINAMICS G120C Converters
44 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals