4.9.1.3 IT system
In an IT line system, all of the conductors are
insulated with respect to the PE protective
conductor or connected to the PE protective
conductor through an impedance.
There are IT systems with and without transfer
of the neutral conductor N.
7UDQVIHURI1LPSHGDQFHZLWK
UHVSHFWWR3(SURWHFWLYHFRQGXFWRU
7UDQVIRUPHURU
JHQHUDWRU
7RWKHV\VWHP
([DPSOH
/
/
/
1
3(
Operating the converter on an IT line system
Converters with integrated line 󹪝lter:
Operation on IT line systems not permissible.
Converter without line 󹪝lter:
Operation on all IT line systems permissible.
Behavior of the converter when a ground fault occurs
You must install an output reactor if the converter is to remain operational even when a ground
fault occurs at the converter output. This output reactor prevents an overcurrent trip or damage
to the converter.
4.9.2 Requirements for the protective conductor
Overview
A high leakage current 󹪞ows through the protective conductor in converter operation. The
protective conductor of the converter must not be interrupted for safe touch protection in
converter operation.
This primarily results in requirements for the minimum conductor cross-section of the
protective conductor.
No restriction applies to the length of the protective conductor for touch protection.
However, short protective conductors are advantageous for EMC-compliant installation.
Installing
4.9Connect the line supply, motor and braking resistor
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 67

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals