Parameter list
SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127
53
Parameter Description Range Factory default Acc. level
P1001[0...2] Fixed frequency 1 [Hz] -599.00 - 599.00 10.00 2
P1002[0...2] Fixed frequency 2 [Hz] -599.00 - 599.00 15.00 2
P1003[0...2] Fixed frequency 3 [Hz] -599.00 - 599.00 25.00 2
P1004[0...2] Fixed frequency 4 [Hz] -599.00 - 599.00 50.00 2
P1005[0...2] Fixed frequency 5 [Hz] -599.00 - 599.00 0.00 2
P1006[0...2] Fixed frequency 6 [Hz] -599.00 - 599.00 0.00 2
P1007[0...2] Fixed frequency 7 [Hz] -599.00 - 599.00 0.00 2
P1008[0...2] Fixed frequency 8 [Hz] -599.00 - 599.00 0.00 2
P1009[0...2] Fixed frequency 9 [Hz] -599.00 - 599.00 0.00 2
P1010[0...2] Fixed frequency 10 [Hz] -599.00 - 599.00 0.00 2
P1011[0...2] Fixed frequency 11 [Hz] -599.00 - 599.00 0.00 2
P1012[0...2] Fixed frequency 12 [Hz] -599.00 - 599.00 0.00 2
P1013[0...2] Fixed frequency 13 [Hz] -599.00 - 599.00 0.00 2
P1014[0...2] Fixed frequency 14 [Hz] -599.00 - 599.00 0.00 2
P1015[0...2] Fixed frequency 15 [Hz] -599.00 - 599.00 0.00 2
P1016[0...2] Fixed frequency mode 1 - 2 1 2
1 Direct selection
2 Binary selection
P1031[0...2] MOP mode - 1 2
P1032 Inhibit reverse direction of MOP 0 - 1 1 2
0 Reverse direction is allowed
1 Reverse direction inhibited
P1040[0...2] Setpoint of the MOP [Hz] -599.00 - 599.00 5.00 2
P1047[0...2] MOP ramp-up time of the RFG [s] 0.00 - 1000.00 10.00 2
P1048[0...2] MOP ramp-down time of the RFG [s] 0.00 - 1000.0 10.00 2
r1050 CO: Actual output freq. of the MOP [Hz] - - 2
P1058[0...2] JOG frequency [Hz] 0.00 - 599.00 5.00 2
P1059[0...2] JOG frequency left [Hz] 0.00 - 599.00 5.00 2
P1060[0...2] JOG ramp-up time [s] 0.00 - 650.00 10.00 2
P1061[0...2] JOG ramp-down time [s] 0.00 - 650.00 10.00 2
P1080[0...2] Minimum frequency [Hz] 0.00 - 599.00 0.00 1
P1082[0...2] Maximum frequency [Hz] 0.00 - 599.00 50.00 1
P1120[0...2] Ramp-up time [s] 0.00 - 650.00 10.00 1
P1121[0...2] Ramp-down time [s] 0.00 - 650.00 10.00 1
P1130[0...2] Ramp-up initial rounding time [s] 0.00 - 40.00 0.00 2
P1131[0...2] Ramp-up final rounding time [s] 0.00 - 40.00 0.00 2
P1132[0...2] Ramp-down initial rounding time [s] 0.00 - 40.00 0.00 2
P1133[0...2] Ramp-down final rounding time [s] 0.00 - 40.00 0.00 2
P1134[0...2] Rounding type 0 - 1 0 2
0 Continuous smoothing
1 Discontinuous smoothing
P1135[0...2] OFF3 ramp-down time [s] 0.00 - 650.00 5.00 2