Parameter list
SINAMICS V20 Inverter
54 Getting Started, 07/2012, A5E03728127
Parameter Description Range Factory default Acc. level
P1200 Flying start 0 - 6 0 2
0 Flying start disabled
1 Flying start always active; searches in both directions
2 Flying start active after power on, fault, OFF2; searches in both directions
3 Flying start active after fault, OFF2; searches in both directions
4 Flying start always active; searches in direction of setpoint only
5 Flying start active after power on, fault, OFF2; searches in direction of setpoint only
6 Flying start active after fault, OFF2; searches in direction of setpoint only
P1210 Automatic restart 0 - 7 1 2
0 Disabled
1 Trip reset after power on, P1211 disabled
2 Restart after mains blackout, P1211 disabled
3 Restart after mains brownout or fault, P1211 enabled
4 Restart after mains brownout, P1211 enabled
5 Restart after mains blackout and fault, P1211 disabled
6 Restart after mains brown- /blackout or fault, P1211 enabled
7 Restart after mains brown- /blackout or fault, trip when P1211 expires
P1215 Holding brake enable 0 - 1 0 2
0 Motor holding brake disabled
1 Motor holding brake enabled
P1216 Holding brake release delay [s] 0.0 - 20.0 1.0 2
P1217 Holding time after ramp down [s] 0.0 - 20.0 1.0 2
P1227[0...2] Zero speed detection monitoring time [s] 0.0 - 300.0 4.0 2
P1232[0...2] DC braking current [%] 0 - 250 100 2
P1233[0...2] Duration of DC braking [s] 0.00 - 250.00 0.00 2
P1234[0...2] DC braking start frequency [Hz] 0.00 - 599.00 599.00 2
P1236[0...2] Compound braking current [%] 0 - 250 0 2
P1237 Dynamic braking 0 - 5 0 2
0 Disabled
1 5 % duty cycle
2 10 % duty cycle
3 20 % duty cycle
4 50 % duty cycle
5 100 % duty cycle
P1300[0...2] Control mode 0 - 19 0 2
0 V/f with linear characteristic 5 V/f for textile applications
1 V/f with FCC 6 V/f with FCC for textile applications
2 V/f with quadratic characteristic 7 V/f with quadratic eco
3 V/f with programmable characteristic
4 V/f with linear eco
19 V/f control with independent voltage
setpoint
P1310[0...2] Continuous boost [%] 0.0 - 250.0 50.0 2
P1311[0...2] Acceleration boost [%] 0.0 - 250.0 0.0 2