Parameter list
SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127
55
Parameter Description Range Factory default Acc. level
P1312[0...2] Starting boost [%] 0.0 - 250.0 0.0 2
P1335[0...2] Slip compensation [%] 0.0 - 600.0 0.0 2
P1336[0...2] Slip limit [%] 0 - 600 250 2
r1348 Economy mode factor [%] - - 2
P1800[0...2] Pulse frequency [kHz] 2 - 16 4 2
P1820[0...2] Reverse output phase sequence 0 - 1 0 2
0 Forward
1 Reverse the Motor
P1900 Select motor data identification 0 - 2 0 2
0 Disabled
2 Identification of all parameters in standstill
r1926 Identified gating unit dead time [μs] - - 2
P2010[0...1] USS / MODBUS baudrate 6 - 12 8 2
6 9600 bps 10 76800 bps
7 19200 bps 11 93750 bps
8 38400 bps 12 115200 bps
9 57600 bps
Index: [0] USS / MODBUS on RS485
[1] USS on RS232 (reserved)
P2011[0...1] USS address 0 - 31 0 2
P2021 Modbus address 1 - 247 1 2
P2023 RS485 protocol selection 0 - 2 1 1
0 None
1 USS
2 Modbus
Notice: After changing P2023, a power-cycle of the inverter (which may take several seconds) is required.
r2110[0...3] CO: Warning number - - 2
P2157[0...2] Threshold frequency f_2 [Hz] 0.00 - 599.00 30.00 2
P2158[0...2] Delay time of threshold freq f_2 [ms] 0 - 10000 10 2
P2159[0...2] Threshold frequency f_3 [Hz] 0.00 - 599.00 30.00 2
P2160[0...2] Delay time of threshold freq f_3 [ms] 0 - 10000 10 2
P2200[0...2] BI: Enable PID controller - 0 2
P2201[0...2] Fixed PID setpoint 1 [%] -200.00 - 200.00 10.00 2
P2202[0...2] Fixed PID setpoint 2 [%] -200.00 - 200.00 20.00 2
P2203[0...2] Fixed PID setpoint 3 [%] -200.00 - 200.00 50.00 2
P2204[0...2] Fixed PID setpoint 4 [%] -200.00 - 200.00 100.00 2
P2205[0...2] Fixed PID setpoint 5 [%] -200.00 - 200.00 0.00 2
P2206[0...2] Fixed PID setpoint 6 [%] -200.00 - 200.00 0.00 2
P2207[0...2] Fixed PID setpoint 7 [%] -200.00 - 200.00 0.00 2
P2208[0...2] Fixed PID setpoint 8 [%] -200.00 - 200.00 0.00 2
P2209[0...2] Fixed PID setpoint 9 [%] -200.00 - 200.00 0.00 2
P2210[0...2] Fixed PID setpoint 10 [%] -200.00 - 200.00 0.00 2