PROFIBUS interface
The PROFIBUS interface is described on the CD of the converter in the document
"Supplementary component descriptions".
PROFIBUS diagnostic LED
Note
A teleservice adapter can be connected to the PROFIBUS interface (X126) for remote
diagnostics purposes.
PROFIBUS address switch
On the CU320-2 DP, the PROFIBUS address is set as a hexadecimal value via two rotary
coding switches. Values between 0
dec
(00
hex
) and 127
dec
(7F
hex
) can be set as the address. The
upper rotary coding switch (H) is used to set the hexadecimal value for 16
1
and the lower rotary
coding switch (L) is used to set the hexadecimal value for 16
0
.
Table A-6 PROFIBUS address switch
Rotary coding switches Significance Examples
21
dec
35
dec
126
dec
15
hex
23
hex
7E
hex
C
D
E
A
B
F
DP
H
1
0
2
3
4
5
6
7
8
9
16
1
= 16 1 2 7
C
D
E
A
B
F
DP
L
1
0
2
3
4
5
6
7
8
9
16
0
= 1 5 3 E
Setting the PROFIBUS address
The factory setting for the rotary coding switches is 0
dec
(00
hex
).
There are two ways to set the PROFIBUS address:
1. Using a parameter
To set the bus address for a PROFIBUS node using STARTER, first set the rotary code
switches to 0
dec
(00
hex
) and/or 127
dec
(7F
hex
).
Use the parameter to set the address to a value between 1 and 126.
For further information, please refer to the converter List Manual.
2. Using the PROFIBUS address switches on the Control Unit
The address is set manually to values between 1 and 126 using the rotary coding
switches. In this case, the parameter is only used to read the address.