Requirements
SIMATIC controller S7-400H with two PROFINET H-CPUs type 41xH
SINAMICS PROFINET Control Unit CU320-2 PN
Redundant communication links
Benefits
No system downtime in the case of a controller failure
Component replacement possible during ongoing operation
Configuration changes possible during ongoing operation
Automatic synchronization after replacing components
Restrictions
IRT is not supported
No simultaneous operation of Shared Device and Shared I-Device
Maximum 2 cyclical PROFINET connections
System redundancy only via the onboard interface of SINAMICS PROFINET Control Unit
For the duration of switching from one controller to the other, the setpoints of the last
connection remain frozen and valid.
Communication
A.1 Communication