11.Define the receive data for node 1:
Specify the data that should be placed in the receive buffer p8872 of node 1 in location
0, received from node 2:
p8872[0] = 2
Define that PZD1 of node 2 is saved in the receive buffer p8870 of node 1 in location 0:
p8870 [ 0] = 1
r2050[0] subsequently contains (after step 13) the value of PZD 1 of node 2.
12.At the two nodes carry-out a "Copy RAM to ROM" to backup the parameterization and the
data.
13.Set p8842 =1, to activate parameters p8870, p8871 and p8872.
6HQGEXIIHU
5HFHLYHEXIIHU
5HFHLYHEXIIHU
6HQGEXIIHU
3='
3='
3='
3='
6,1$0,&6/LQN
3DUWLFLSDQW
6,1$0,&6/LQN
3DUWLFLSDQW
U$FWXDOVSHHGVPRRWKHG
U7RWDOWRUTXHVHWSRLQW
U&RQWUROZRUGVHTXHQFHFRQWUROGULYH
U6WDWXVZRUGVHTXHQFHFRQWUROGULYH
U>@3='SDUWLF
S>@ 
S>@ 
U>@GULYHU3='
S>@ 
'ULYHREMHFW
1DPH GULYH
'ULYHREMHFW
1DPH GULYH
U>@ 3='SDUWLF
U>@ 3='SDUWLF
U>@ 3='SDUWLF
S>@ 
S>@ 
S>@ 
S>@ 
S>@ 
S>@ 
S>@ 
S>@ 
S>@ 
S>@ 
S>@ GULYHU3='
S>@ GULYHU3='
S>@ GULYHU3='
S>@ 
S>@ 
S>@ 
S>@ 
S>@ 
S 
S 
S 
S>@ 
S>@ 
&8&8
S 
S 
S 
S>@ 
S>@ 
Figure A-40 SINAMICS Link: Configuration example
Communication
A.1 Communication
Industrial Security
Configuration Manual, 08/2017, A5E36912609A 213