Built-In PLC Application
SINUMERIK 801 3-9
Start-Up
14510[2]
Definition: Interval of track lubrication
Unit: 1 minute
Range: 5~300 minutes
14510[3]
Definition: Duration of lubrication
Unit: 0.1 second
Range: 10~200 (1~20 seconds)
14510[4]
Definition: Number of positions on the turret
Unit: -
Range: 4 or 6
14510[5]
Definition: Monitor time (turret change abort if destination tool not
found within specified time)
Unit: 0.1second
Range: 30~200 (3~20 seconds)
14510[6]
Definition: Turret clamping time
Unit: 0.1 second
Range: 5~30 (0.5~3 seconds)
14510[7]
Definition: Braking time of external brake mechanism of a
contactor controlled spindle
Unit: 0.1 second
Range: 5~200 (0.5~20 seconds)