Start-Up
4.3 Starting up the PLC
4-53
SINUMERIK 802C
6FC5 5973AA200BP2 (01.02)
Possible alarm responses are:
S PLC Stop : The user program is no longer executed, the NC Ready relay drops out, and
the hardware outputs are disabled ( OUTDS ).
S EMERGENCY STOP: The PLC provides the EMERGENCY STOP signal to the NCK in
the user interface after the user program has been executed.
S Feed disable: The PLC provides the Feed Disable signal to the NCK in the user interface
after the user program has been executed.
S Readin disable: The NCK provides the Readin Disable signal to the NCK in the user
interface after the user program has been executed.
S NC Start inhibited: The PLC provides the NC Start Inhibited signal to the NCK after the
user program has been executed.
S SHOWALARM : This alarm has no alarm response (bit0 bit5 =0).
Priority of cancel conditions
The cancel conditions have the following priority:
S POWER ON CLEAR system alarms (highest priority)
S CANCEL CLEAR system alarms
S SELFCLEARING system alarms
S POWERON CLEAR user alarms
S CANCEL CLEAR user alarms
S SELFCLEARING user alarm (lowest priority)
System alarms
see Diagnostics Guide
User alarms
The user interface 1600xxxx provides the user with two subranges for setting a user alarm.
S Subrange 0: 4 x 8 bits to set user alarms (0 > 1 edge)
Byte 0 : Bit0 => 1st user alarm ‘’ 700000 ‘’
Byte 3 : Bit7 => 32nd user alarm ‘’ 700031 ’’
S Subrange 1: User alarm variables
The respective bit (subrange 0) with a 0/1 edge change will activate a new user alarm.
Subrange 1 is intended for additional user information.
Subrange 2 can be used to analyze the active alarm responses.
Subrange 1 can only be read or written as a double word. Subrange 2 can only be read.
You can delete selfclearing alarms by resetting the respective bit in the variable range
‘’1600xxxx’’ in subrange 0 (1 > 0 edge).
The remaining user alarms are cleared by the PLC after detecting the respective cancel condi-
tion. If the alarm is still present, the alarm occurs again.

Table of Contents

Other manuals for Siemens SINUMERIK 802C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK 802C and is the answer not in the manual?

Siemens SINUMERIK 802C Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK 802C
CategoryControl Systems
LanguageEnglish

Related product manuals