3. Hazardous shock voltages caused by, for example:
Component failure
Influence during electrostatic charging
Induction of voltages in moving motors
Operation and/or environmental conditions outside the specification
Condensation/conductive contamination
External influences/damage
4. Electrical, magnetic and electromagnetic fields generated in operation that can pose a risk
to people with a pacemaker, implants or metal replacement joints, etc., if they are too close
5. Release of environmental pollutants or emissions as a result of improper operation of the
system and/or failure to dispose of components safely and correctly
6. Influence of network-connected communication systems, e.g. ripple-control transmitters or
data communication via the network
For more information about the residual risks of the drive system components, see the relevant
sections in the technical user documentation.
1.2 Application planning
1.2.1 Secondary electrical conditions
1.2.1.1 Power supply
Requirements for DC power supplies
DANGER
Danger of death caused by unsafe power supply
The DC power supply must be implemented as a circuit of Category PELV/DVC A according
to EN 61800-5-1.
General information and networking
1.2 Application planning
Operator panel front: OP 010
Manual, 07/2018, A5E36371538B 11