EasyManua.ls Logo

Siemens SIPROTEC 7SD610 - Page 110

Siemens SIPROTEC 7SD610
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
2.9 Backup Time Overcurrent Protection
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
110
Figure 2-43 Logic diagram of the I
P
stage (directional, inverse time overcurrent protection), for example IEC character-
istics
1
) Output indications associated with the pickup signals are listed in Table 2-3
2
) Output indications associated with the trip signals are listed in Table 2-4
3
) The indications „O/C L2 forward“, „O/C L3 forward“, „O/C L2 reverse“, „O/C L3 reverse“ have
not been represented in the Figure, however, they are reported if necessary.

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Related product manuals